Basically, stack temperature and percentage of CO
2
are a measure
of stack losses for any fuel. Therefore, many of the basic principles
can be and should be applied to oil-fired furnaces as well as for
those burning solid fuels.
In preparation for these tests, the following should be checked. The
Draft Regulator installed should be:
plumb and level
in the same room as the unit
on the side of a vertical, sloping or horizontal smoke pipe
located close to the furnace
Drill two holes approximately 1/4 inch in diameter in the flue pipe
between the outlet from the furnace and the Draft Control.
Insert a stack thermometer in one of the holes and leave it there
continually during the test so that you can refer to it at any time.
(See Fig. 20.)
TEST PROCEDURE
Step 1. Set the thermostat high enough so that the unit will run for
at least 15 minutes, t
he maximum time that should be required for the test. Let the unit
operate enough for the stack temperature to stabilize.
Step 2. For your initial set of readings, set the Draft Regulator so
that there is .03 Water Column Draft in the smoke pipe between
the flue outlet and draft regulator. (See Fig. 20.)
Fig. 20
Step 3. Insert the sampling tube of the CO
2
tester in the hole that
you have drilled adjacent to the stack thermometer and find the
percentage of CO
2
in the sample of the products of combustion.
Follow the instructions of the manufacturer of the instrument you
are using.
Step 4. Use efficiency finder chart or stack loss slide rule to deter-
mine efficiency. (See Fig. 21.) Be sure to subtract room tempera-
ture from stack thermometer reading and use this net stack tem-
perature for determining the efficiency.
Step 5. Insert end of smoke tester into same hole as was used to
test for CO
2
and perform the smoke test.
Step 5. The filter paper from the smoke test, when compared to
the standard, must be determined and be found to be satisfactory.
It should never be greater than #2, preferably #1 or zero, depend-
ing on local requirements or your own service standard. (See Fig.
21.)
Repeat steps 3, 4, and 5 as needed, adjusting the air shutter on the
burner and draft regulator until you obtain the highest possible effi-
ciency. It is desirable to have a high CO
2
reading and low stack
temperature with a minimum smoke reading.